HomeProductsData center/tower/base stationAMC Series Data Center Monitoring ModuleAMC16Z-FDK24/48 DC multi-circuit energy meter

AMC16Z-FDK24/48 DC multi-circuit energy meter

AMC16Z series DC precision power distribution monitoring meter is a measuring instrument designed for data center server power management. The instrument is exquisitely designed and can monitor the electrical parameters, switching status and input and output parameters of lightning protection device of A+B, two incoming lines and 96 channels in real time, and all alarm threshold measurement channels can be set separately to achieve the limit of sound and light alarm of limited event trigger system, and instantly integrate the volume and height monitoring circuit into the traditional instrument.

  • Specially designed for powering servers in data centers
  • A+B Independent branch circuits [24 or 48] (total)
  • U, I, P, Q, S, PF, kWh, kvarh
  • 2nd ~ 31st harmonic
  • kWh class 0.5
  • DIN rails 35mm
  • Certificates: LVD, EMC

Product info

DC multi-circuit energy meter
12 or 24 channels of each branch circuit of A+B
Independent 2-circuit of the output current
1 RS485 communication
potency, reactivity
2nd-31st harmonic
A+B Independent branch circuits:[24 or 48] (total)
Frequency:45~60Hz
Auxiliary care:direct current 12V / 24V
Installation:DIN rails 35 mm
Dimension (L*W*H):180*94.3*45mm
Power supply by AMC16Z-ZD; DC 12-24V when used alone

Technical data

product models

AMC16Z-ZA A+B independent 2-channel three-phase input U, 1, P, Q, S, PF, EP, EQ, UN to PG, neutral current 2-63rd harmonic voltage and current 6-channel passive switch input 2-channel switch output RS485 (Modbus RTU) communication
AMC16Z-ZD Measuring voltage and current of A+B independent bidirectional DC bus Kw、Kwh、6DI+2DO+1 RS485(Modbus-RTU)
AMC16Z-KA A+ B independent 2-way one-sidedness 24 active switching states
AMC16Z-KD A+ B independent 2-way single-sided 24-pole switching state
AMC16Z-FAK24 Measurement of A+B two-way AC socket, total 24 branches fully electrical parameters and switching value status, 1RS485 (Modbus-RTU)
AMC16Z-FAK48 Measurement of A+B two-way AC socket, total 48 branches full electrical parameters and switching value status, 1RS485 (Modbus-RTU)
AMC16Z-FDK24 Measure A+B two-way DC output, total 24 branches fully electrical parameters and switching value/status, 1RS485(Modbus-RTU)
AMC16Z-FDK48 A+B two-way DC output measurement, total 48 branches fully electrical parameters and switching value status, 1RS485 (Modbus-RTU)

product features

Monitoring of dual DC output circuits

● A + B monitoring of the two-sided independent DC circuits

● Complete monitoring of electrical parameters

● Multi-metering for outgoing branch circuits

measurement of multiple circuits

● Both 1-phase and 3-phase measurement

● Max. 36 single-phase circuits

● Max. 12 3-phase circuits

● Mixed: 8 circuits, 3-phase and 12 circuits, 1-phase, for example

analysis of network quality

● 2nd ~ 31st harmonic

● Total harmonics

Turn status detection on/off

● A+B on both sides

● 48-channel DI (digital input)

Technical parameters

Model

AMC16Z-FDK24

AMC16Z-FDK48
measurement parameters
Voltage, current, frequency, active power, reactive power, power factor, switching state
2nd ~ 31st harmonic
nominal voltage of the bus
DC48V, DC240V, DC336V (±20%)
current output circuit
Nominal value
5V (Hall sensor, external power supply ±12V)
Area
Measurement accuracy
Outgoing line Voltage/current level 0.5, power/electrical energy level 1
input frequency
45~60Hz
Auxiliary power supply Power supply by AMC16Z-ZD; DC 12-24V when used alone
Environment temperature

Working temperature: -15 °C ~ 55 °C

Storage temperature: -25 °C ~ 70 °C

moisture Relative humidity≤93%
Height ≤2500m
communication RS485/Modbus-RTU
installation method DIN35mm guide rail or base plate mounting
IP protection class IP20
pollution class 2
Security insulation All terminals and the insulation resistance between the conductive pieces not less than 100 MΩ
dielectric strength A-channel switch input signal // B-channel switch input signal // other ports meet AC2kV 1 minute between pairs, leakage current should be less than 2mA, no breakdown or flashover
Electromagnetic compatibility Antistatic interference level 4
Resistance to radiation from high-frequency electromagnetic waves level 3

Product display

similar products