HomeProductsData center/tower/base stationAMC Series Data Center Monitoring ModuleAMC100-ZA AC precision device for monitoring power distribution

AMC100-ZA AC precision device for monitoring power distribution

Acrel's AMC100 series AC power monitoring devices is a measuring instrument designed for data center server power management. The compact design of the device enables real-time monitoring of all electrical parameters, input and output switches, and arrester status of two incoming and 192 outgoing A+B lines. The AMC100 series precision power distribution monitoring devices are used in IDC data centers such as finance, operators, government and IT. The product can be flexibly configured to monitor and centrally manage power consumption in the entire data center in real time.

  • Monitors the voltage, current, power and electrical energy of 2 independent incoming lines A+B
  • 8 digital inputs, 4 digital outputs
  • 1-channel temperature and humidity monitoring
  • 3 channels RS485 Modbus-RTU
  • 2nd-63rd harmonic
  • Certificates: LVD, EMC

Product info

Voltage, current, frequency, active power, reactive power, power factor, active energy, reactive energy, measurement of total power parametersZero-ground voltage, leakage current and zero-sequence current, 2-63 harmonics
180mm width8DI4DO+1 channel temperature and humidity
Ethernet (optional)3 RS485 channels (2 uplink touchscreens and movable ring, 1 downlink submodule)
Nominal bus voltage: AC 220V(±20%) 
Rated current of the input circuit: secondary level 5A
Temperature range:-40℃~+99℃
Input frequency:AC 45~65Hz
Measurement accuracy:Voltage/current level 0.2, active energy level 0.5, reactive energy level 1
Operating temperatur:-20℃~150℃ 
Switching output:4 channels 3A 250VAC/3A 30VDC
Installation method: DIN35mm rail or base plate mounting

Technical data

product models

AMC100-ZA Measurement of all electrical parameters of A+B independent 2-channel AC three-phase input, 8Dl/4D0, 2-channel leakage current monitoring, 1-channel temperature and humidity monitoring, 2-63 harmonics, 3-channel RS485 Modbus RTU (1 for branch module, 1 for HMl, 1 for monitoring system)
AMC100-FA30 Measurement of A+B independently 30 channels AC socket all electrical parameters, 1 channel RS485 Modbus-RTU
AMC100-FA48 Measurement of A+B independently 48 channels AC socket all electrical parameters, 1 channel RS485 Modbus-RTU
AMC100-ZD Measurement of A+B independent 2-channel DC inputs, U,l,P,Q, 8Dl/4D0, 1 channel temperature and humidity monitoring, 3 channels RS485 Modbus-RTU ((1 for branch module, 1 for HMl, 1 for monitoring system)
AMC100-FD30 Measurement of A+B independently, 30 channels DC output all electrical parameters, 1 channel RS485 Modbus-RTU
AMC100-FD48 Measurement of A+B independently 48 channels DC output all electrical parameters, 1 channel RS485 Modbus-RTU
AMC100-FAK30 Measurement of A+B independent 30 channels AC socket, all electrical parameters and switching value status, 1 channel RS485 Modbus-RTU
AMC100-FAK48 Measurement of A+B independent 48 channels AC socket, all electrical parameters and switching value status, 1 channel RS485 Modbus-RTU
AMC100-FDK30 Measurement of A+B independent, 30 channels DC output, all electrical parameters and switching value status, 1 channel RS485 Modbus-RTU
AMC100-FDK48 Measurement of A+B, independent, 48 channels, DC output, all electrical parameters and switching value status, 1 channel RS485 Modbus-RTU

 

Technical parameters AMC100-ZA
measurement parameters Voltage, current, frequency, active power, reactive power, power factor, active energy, reactive energy, zero-ground voltage, leakage current and zero-sequence current, total harmonic distortion (THD), 2-63 harmonics, current and voltage unbalance, ambient temperature and humidity
bus nominal voltage AC220V
measuring range ±20%
overloading Instantaneous voltage 2 times/sec
Incoming circuit Rated current secondary level 5A
Area 0~6A
overloading Continuously 1.2 times, immediately 10 times/s
Temperature range -40℃~+99℃
Humidity Range 20%~90%
input frequency AC 45~65Hz
Measurement accuracy Incoming line Voltage/current level 0.2, active power/energy level 0.5, reactive power/energy level 1
temperature ±1℃
moisture ±5%
Auxiliary energy AMC100-ZA: Power consumption signal (≤15W)
AMC100-ZA-P220: 220V independent power supply
AMC100-ZA-P24: DC 12-24V independent power supply
operating temperatur -20℃~150℃
Storage temperature -25℃~70℃
Height ≤2500m
Switching output 4 channels 3A 250VAC/3A 30VDC
communication 1 isolated RS485/Modbus-RTU to the background system
1 RS485/Modbus-RTU on touchscreen
1 downstream module with RS485/Modbus-RTU connection
Optional 1-channel Ethernet communication function
installation method DIN35mm rail or base plate mounting
level of protection protection class IP20
degree of contamination 2

Product display

similar products