accuracy
Voltage: 0.2, Current, Power, Active energy: 0.5, Frequency: 0.01 Hz, Reactive energy: 1
frequency
45–65 Hz
Power consumption
≤10 VAp>
Power supply output
AC 85-265V or DC 100-350V
Input power
Under 0.2 VA
accuracy
Voltage: 0.2, Current, Power, Active energy: 0.5, Frequency: 0.01 Hz, Reactive energy: 1
frequency
45–65 Hz
Power consumption
≤10 VAp>
Power supply output
AC 85-265V or DC 100-350V
Input power
Under 0.2 VA
Use in decentralized and centralized photovoltaics ● Rogowski coils for centralized photovoltaics ● Split-core current transformer for decentralized photovoltaics ● Backflow monitoring ● Harmonic monitoring |
![]() |
Bidirectional measurement ● Active energy measurement ● Reactive energy measurement |
![]() |
RS485 communication ● MODBUS-RTU protocol ● Communicate with the inverter to achieve the backflow prevention function |
![]() |
Coupled with external current transformers or Rogowski coil ● Rated current of the current transformers: up to 300 A ● Rated current of the Rogowski coil: up to 20,000 A |
![]() |
LCD display ● Parameter display ● Programming interface |
![]() |
Control panel HMI for programming ● Parameter display ● Communication (address, baud rate, etc.) ● Wiring: 3P3W, 3P4W |
![]() |
Function/Model |
ACR10RH-DxxT(R)E4 ACR10RH-DxxT(R)E3 |
|
display mode |
LCD (Field LCD) |
■ |
measurement parameters |
Current/Voltage/Frequency/Power Factor |
■ |
Active power/reactive power/apparent power |
■ |
|
Four-quadrant measurement of electrical energy |
■ |
|
Maximum demand |
□ |
|
Metering of electrical energy with multiple tariffs |
□ |
|
Power quality monitoring |
Overall harmonic content |
■ |
Subharmonic (2-31 times) |
■ |
|
Data logging |
Incident recording |
□ |
display mode |
alarm |
□ |
Built-in clock |
□ |
|
communication |
RS485 interface |
■ |
Optional feature (select one) |
J(2DO) |
A1+ (B1 or C1) |
K(4DI) |
||
Pulse (2 channels) |
A notice:
1. "■" is the default assignment function, "□" is the mapping function. The above device uses 1-channel RS485 communication by default.
2. The connection mode corresponds to A1/B1/C1 etc. in the selection function.
3. Pulse output and relay output cannot be selected at the same time.
4. If you select the event logging function, you need to configure the DI or DO port.
Technical parameters |
Indicators |
|||
Entrance |
Phase line |
3-phase 3-wire, 3-phase 4-wire |
||
frequency |
45~65Hz |
|||
voltage |
Rated power: AC 57.7V/100V (100V), 220V/380V (400V) |
|||
Overload: 1.2 times power (continuous); 2 times power/1 second |
||||
Consumption: <0.2 VA |
||||
Electricity |
Rated power: 80 A, 120 A, 200 A, etc. (see specific product specifications, special parameters can be customized) |
|||
Overload: 1.2 times power (continuous); 10 times power/1 second |
||||
Consumption: < 0.2 VA |
||||
output |
Electrical energy |
Output mode: open collector optocoupler pulse, two-way output |
||
Three-phase |
Pulse constant: 4000, 8000 Imp/kWh |
|||
communication |
RS485 interface, Modbus RTU protocol |
|||
display mode |
LCD |
|||
function |
Switch |
Entrance |
Four-way dry contact input |
|
output |
Output mode: two-way relay NO contact output |
|||
Contact capacity: AC 250V/3A, DC 30V/3A |
||||
Measurement accuracy |
Frequency 0.05 Hz, reactive energy 1 class, other 0.5 class |
|||
Power supply |
AC85-265V or DC100-350V; DC24V (±10 %); DC48V (±10 %) |
|||
Security |
Power frequency withstand voltage |
The power frequency withstand voltage between auxiliary power and switching volume output and current input and voltage input and communication and pulse output and switching volume input terminal is AC 2 kV 1 min.; The power frequency withstand voltage between auxiliary power and switching volume output and current input voltage input terminal is AC 2 kV/1 min.; The power frequency withstand voltage between communication and pulse output and switching volume input terminal is AC 1 kV/1 min.; |
||
Insulation resistance |
Input, output connection to the housing>100MΩ |
|||
Environment |
Operating temperature: -10 °C to +55 °C; Storage temperature: -20 °C to +70 °C; Relative humidity: 5 °C to 95 °C (no condensation); Altitude: ≤ 2500 m |
Product display