ADF400L multi-circuit energy meter

The ADF400L multi-circuit energy meter can implement direct access measurements of 12 three-phase channels or 36 single-phase channels, or mixed measurements of 12 three-phase channels with transformer access measurement, direct access, and transformer access through module combinations. Its high accuracy, centralized installation, centralized management, and high installation flexibility provide advantages for municipalities, schools, and businesses, including interference prevention and other benefits. A prepaid option is now available.

  • Application: Prepaid and Postpaid
  • Monitoring: Up to 36 single-phase circuits or 12 three-phase or mixed circuits
  • Measurement: 1-phase and 3-phase kWh (class 0.5S), kVarh, active power, reactive power, current, voltage, etc.
  • Rated voltage: 3x220/380 V (50 Hz)
  • Rated current: 80 A AC (direct connection); 3x1(6)A AC (via current transformer)
  • Communication (main part): RS485 (MODBUS-RTU); Ethernet; Infrared
  • Communication (extended): 4G; Wi-Fi; LoRa
  • Remote control: DO&DI
  • Installation: 35 mm DIN rail
  • Power supply: 3*220/380 V or 220 V AC
  • Standard and certificate: CE

Product info

Technical data

characteristics

Compact modular design

● Main unit (LCD display and control panel)

● 1-phase measuring module

● 3-phase measuring module

● Advanced communication module

Multi-circuit measurement for 1- and 3-phase circuits

● Three types of multi-circuit combination

● Max. 36 circuits (1-phase measurement)

● Max. 12 circuits (3-phase measurement)

● Mixed measurement (1- and 3-phase circuits)

Remote control of the switches

● Control and read switch status

● 2 DO & 2 DI (main module)

● Dry contact DI (main module)

● 4 DO & 4 DI (CT-operated submodule)

● 220 V AC wet contact DI (CT-powered submodule)

Module overview

Main part

● Maximum 36 single-phase circuits or 12 three-phase circuits

● Max. 12 modules (1-phase) or 6 modules (3-phase)

● RS485 (MODBUS-RTU), Ethernet

● LCD keypads HMI

Submodule (connection via CTs)

● Monitor a maximum of 2 circuits, 3 phases

● 3x1(6)A AC (CT-powered connection)

● 4DO and 4DI (220 V AC wet contact DI)

● LED display

Submodule (direct connection)

● Monitoring of max. 3 single-phase or 1 three-phase circuits

● Max. 80 A AC direct load current

● LED display

Communication module

● Uplink: 4G/WiFi/LoRa/LoRaWAN/NB-IoT

● Downlink: RS485 (MODBUS-RTU)

● RJ45 interface (connection to the host)

● Power supply: 24 V/12 V DC or 220 V AC/DC

 

parameter Description and value
Auxiliary power supply
Tension

3 x 220 V/380 V (for 3-phase sub-modules); 220 V AC (for 1-phase sub-modules)

Power consumption

≤10W

Input voltage
nominal voltage 3 x 220/380V AC (three phase); 220V AC (single phase)
frequency 50Hz
Input current
Rated current Max. 80 A load current (for 1-phase 3-phase sub-module with direct connection); 3×1(6)A (for 3-phase sub-module via CTs)
Starting current 1 ‰ Ib (class 0.5 S)
accuracy
measurement Class 0.5
Clock ≤0.5s/d
pulse
Pulse output 1 active energy pulse per 3-phase submodule
Pulse width 80ms±20ms
Impulse constant 6400 pulses/kWh (3-phase)
communication
RS485 MODBUS RTU
Infrared For scanning prepaid cards
Ethernet MODBUS TCP
Environment
operating temperatur -20℃~+60℃
Storage temperature -30℃~+70℃
humidity ≤95% (No condensation)
Height <2000m