HomeProductsIsolated energy distributionMedical IT Isolated Power SystemAID120 remote alarm indicator

AID120 remote alarm indicator

The AID120 is typically used in combination with the AIM-M100. Data exchange takes place via RS485 communication. It is suitable for installation in the interior wall of operating rooms or nursing stations and can monitor multiple AIM-M100 insulation monitoring devices. It features audible and visual alarm functions for events such as insulation, overload, overtemperature, and device failure. It is equipped with a digital display and RS485 communication functions.

  • Remote monitoring
  • LED indicators: On, Isolation, Overload, Overtemperature
  • Mute button
  • Test button
  • Auxiliary power supply: DC 24 V
  • RS485 (MODBUS RTU)

Product info

Technical data

Auxiliary energy voltage DC24V
consumption
<0.6W
Insulation measuring range
10–999 kΩ
Isolation alarm area
50~999kΩ
Transformer load rate
Percentage display
Settings for the charging current alarm value
14A, 18A, 22A, 28A, 35A, 45A
Temperature alarm value range
0-200℃
alarm Sound and light alarm
Alarm type Insulation fault, overload, overtemperature, device failure
communication RS485 interface, Modbus RTU protocol
Advertisement LCD display

Product display