HomeProductsData center/tower/base stationAMC Series Multi-Circuit DC Energy MetersAMC16(L)-DETT multi-circuit DC energy meter

AMC16(L)-DETT multi-circuit DC energy meter

Acrel AMC16(L)-DETT Base Station DC Energy Meter for 4G/5G Tower is specially designed for base stations where common requirements exist and switching power supply is without the function of sub-user measurement. The energy meter could measure 6 circuits DC current and supply working current to the matching hall sensors. Meanwhile, it can realize zero drift calibration by upper computer software.have the functions of telemetering, teleindication, teleadjustment, real-time measurement, power quality abnormal alarm, data storage and processing, data interaction.

  • Measurement: Up to 6 DC circuits and one additional AC circuit
  • Measurement: Monitor device system time, total voltage, total output current, power, energy, each channel voltage, current, power, energy and etc.
  • Genauigkeit: 1%In≤I≤10%Im Fehler±2.5%; I>10%Fehler±2%
  • Rated voltage: DC-48V [1-channel DC input]
  • Rated current: DC5V [via -/5Vdc Hall sensor]
  • Communication: RS485 (MODBUS-RTU)
  • Auxiliary power supply: DC-40~-60V
  • Output power: +12V/100mA, -12V/50mA[supplied to 6 coupled hall sensors]
  • Display: LED indicator light (AMC16-DETT)/ LCD display (AMC16L-DETT)
  • Certificates: CE

Product info

Auxiliary power supply: DC-40~-60V

Hall Sensor Power Supply: +12V/100mA, -12V/50mA

Communication: Single-channel RS485

Communication protocol: standard or customer-specific

Working temperature: -20℃~+60℃

Storage temperature: -40℃~+70℃

Altitude: ≤4000m

Installation: 35mm DIN rail

Storage function: It has the storage function of historical performance data and historical
alarm information, and the memory is 2MB.

Technical data

multi-circuit measurement
 
● Monitoring of up to 6-circuit DC circuits
 
● Nominal voltage [DC]: -48Vdc
 
● Nominal current [DC]: 5Vdc [via hall sensor]
 
● 1 additional supply voltage monitoring [via -/5Vdc converter]
 

Wired communication

 

● 1-way RS485 interface

 

● MODBUS-RTU protocol

 

● Baud rate: 9600 standard [optional 1200, 2400, 4800]

 

● Wiring cable recommended: RVSP 2x1.5²mm

Additional output power
 
● Application: 6 pairs of Hall sensors ± 12 VDC output
 
● Output specifications: +12V / 100mA, -12V / 50mA

 

Technical parameters index
input DC nominal voltage 1-channel: DC -48V
DC Aktuell 6-channel hall sensors: total 200A/5V, China Telecom, China Mobile, China Unicom and the first channel reserve 50A/5V, second channel reserve 100A/5V.
monitoring of commercial power supply 1-channel: DC 0~5V
overload capacity Voltage:1.2 times continued,2 times continued 1s;
Current: 1.2 times continued, 10 times continued 1s.
accuracy (overlay hall sensors) 1%In≤I≤10%Im Fehler±2.5%; I>10%Fehler±2%
measurement resolution
Voltage output accuracy 0.01V; Current output accuracy 0.01A;
Output accuracy 0.01kw; Energy output accuracy 0.01kwh
function basic function Monitor device system time, total voltage, output total current, power, energy, each channel voltage, current, power, energy; LED display; 485 communication
measuring function
Starting current: Under rated voltage, when the load current value of the meter does not exceed 1% of the maximum current, the meter starts.
Shunt run current: When there is no current in the meter circuit and 85%-125% of the rated voltage is applied to the voltage circuit, the calculator must not have more than one digital change.
alarm function DC output low alarm, DC output high alarm, power off alarm, module voltage loss alarm, measurement branch error alarm, internal program error alarm, alarm clock error alarm, memory failure alarm, AC input power failure alarm
timing function Support broadcast timing, could remote timing to the meter through RS485 communication.
communication Single channel RS485, baud rate 9600bps, can be set to 1200BPS, 2400bps, 4800bps. Communication protocol: standard or customized
Hall sensor power supply Power supply: +12V/100mA, -12V/50mA
clock accuracy ≤0.5S/d(23), ≤1S/d(-20-60),
Auxiliary power supply Voltage range DC -40V~-60V
Power consumption Whole machine ≤ 2W (no Hall power output)
memory function It has the storage function of historical performance data and historical alarm information, and the memory is 2MB
insulation resistance ≥40MΩ
Environment temperature Working temperature: -20℃~+60℃ Storage temperature: -40℃~+70℃
moisture ≤98% no condensation, no corrosive gas spot
Height ≤4000m
level of protection IP 20
installation 35mm DIN rail

Product display