HomeProductsData center/tower/base stationAMC Series Data Center Monitoring ModuleAMC16Z-FAK24/48 AC multi-circuit energy meter

AMC16Z-FAK24/48 AC multi-circuit energy meter

Acrel AMC16Z-FAK series can monitor the complete power parameters and switching status of 24 or 48 branches of dual-channel AC outlet, 1-channel RS485 communication and phase matching. AMC16Z-FAK24 and AMC16Z-FAK48 are widely used for precise power distribution monitoring equipment in data centers.

  • Specially designed for powering servers in data centers
  • A+B Independent branch circuits [24 or 48] (total)
  • U, I, P, Q, S, PF, kWh, kvarh
  • 2nd ~ 31st harmonic
  • kWh class 0.5
  • DIN rails 35mm
  • Certificates: LVD, EMC

Product info

AC multi-circuit energy meter
12 or 24 channels of each branch circuit of A+B
Independent 2-circuit of the output current
1 RS485 communication
potency, reactivity
2nd-31st harmonic
A+B Independent branch circuits:[24 or 48] (total)
Frequency:45~60Hz
Installation:DIN rails 35 mm
Dimension (L*W*H):180*94.3*45mm
Power supply by AMC16Z-ZA; DC 12-24V when used alone

Technical data

product models

AMC16Z-ZA A+B independent 2-channel three-phase input U, 1, P, Q, S, PF, EP, EQ, UN to PG, neutral current 2-63rd harmonic voltage and current 6-channel passive switch input 2-channel switch output RS485 (Modbus RTU) communication
AMC16Z-ZD Measuring voltage and current of A+B independent bidirectional DC bus Kw、Kwh、6DI+2DO+1 RS485(Modbus-RTU)
AMC16Z-KA A+ B independent 2-way one-sidedness 24 active switching states
AMC16Z-KD A+ B independent 2-way single-sided 24-pole switching state
AMC16Z-FAK24 Measurement of A+B two-way AC socket, total 24 branches fully electrical parameters and switching value status, 1RS485 (Modbus-RTU)
AMC16Z-FAK48 Measurement of A+B two-way AC socket, total 48 branches full electrical parameters and switching value status, 1RS485 (Modbus-RTU)
AMC16Z-FDK24 Measure A+B two-way DC output, total 24 branches fully electrical parameters and switching value/status, 1RS485(Modbus-RTU)
AMC16Z-FDK48 A+B two-way DC output measurement, total 48 branches fully electrical parameters and switching value status, 1RS485 (Modbus-RTU)

product features

monitoring of dual AC output circuits

● A + B monitoring of the two-sided independent AC circuits

● Complete monitoring of electrical parameters

● Multi-metering for outgoing branch circuits

measurement of multiple circuits

● Both 1-phase and 3-phase measurement

● Max. 36 single-phase circuits

● Max. 12 3-phase circuits

● Mixed: 8 circuits, 3-phase and 12 circuits, 1-phase, for example

analysis of network quality

● 2nd ~ 31st harmonic

● Total harmonics

Turn status detection on/off

● A+B on both sides

● 48-channel DI (digital input)

Technical parameters

Model

AMC16Z-FAK24

AMC16Z-FAK48
measurement parameters
Voltage, current, frequency, active power, reactive power, power factor, switching state
2nd ~ 31st harmonic
nominal voltage of the bus
AC 220V(±20%)
current output circuit
Nominal value
50mA
Area 0.125-60mA
Measurement accuracy
Outgoing line Voltage/Current/Active Power/Active Energy Level 0.5, Reactive Power/Reactive Energy Level 1
input frequency
45~60Hz
Auxiliary power supply Power supply by AMC16Z-ZA; DC 12-24V when used alone
Environment temperature

Working temperature: -15 °C ~ 55 °C

Storage temperature: -25 °C ~ 70 °C

moisture Relative humidity≤93%
Height ≤2500m
communication RS485/Modbus-RTU
installation method DIN35mm guide rail or base plate mounting
IP protection class IP20
pollution class 2
Security insulation All terminals and the insulation resistance between the conductive pieces not less than 100 MΩ
dielectric strength A-channel switch input signal // B-channel switch input signal // other ports meet AC2kV 1 minute between pairs, leakage current should be less than 2mA, no breakdown or flashover
Electromagnetic compatibility Antistatic interference level 4
Resistance to radiation from high-frequency electromagnetic waves level 3

Product display