Three-phase multifunction power meter | |
Communication: | RS485(Modbus RTU) |
Advertisement: | LCD display |
Rated current: | 5A AC or 1A AC (via CTs) |
Measurement accuracy: | Active energy: Class 0.5 |
Nominal voltage: | 400 V or 660 V AC LL (direct connection); 100 V AC LL (via PTs) |
Installation: | Panel mounted |
Dimension (LBH): | Panel size (L×W): 75*75mm Cutout(L×W): 67*67mm Depth (H): 94.3mm |
Optional functions | |
/H: | THDi, THDu, 2-31st harmonics |
/SOE: | Event recording |
/K: | 4DI/2DO |
/KM: | 2D1/2DO/1M |
/F: | Multiple tariffs |
Auxiliary power supply: | 85-265V AC/DC; 24V or 48V DC |
AMC96L-E4/KC Three-phase multifunction power meter
The Acrel AMC series programmable intelligent electrical meter integrates the measurement of all power parameters (such as single-phase or three-phase current, voltage, active power, reactive power, apparent power, frequency, power factor, etc.), multi-tariff energy metering, four-quadrant power metering, harmonic analysis, and power monitoring and evaluation management. A variety of peripheral interface functions via the LCD display enable parameter setting and control via the panel keys, making it ideal for real-time power monitoring systems.
Product info
Technical data
Technical parameters | Numerical | ||
Entrance | Nominal value |
AC voltage: three-phase AC 100 V, 400 V, 660 V AC; Current: AC 1 A, 5 A; |
|
overload | Voltage: 1.2 times rated value (continuous current); 2 times rated value/1 second Current: 1.2 times rated value (continuous current); 10 times rated value/1 second |
||
frequency | 45Hz~65Hz | ||
Power consumption | The power consumption of each voltage and current input circuit is less than 0.5 VA | ||
accuracy | 0.5 class | ||
function | Advertisement | LED or LCD | |
communication | RS485, Modbus RTU protocol; (1 start bit, 8 data bits, 1 stop bit, no parity) Baud rate 2400/4800/9600/19200 bps etc. | ||
alarm | 1-channel passive relay, contact capacity 3A/30 VDC, 3A/250 VAC, used for high, low, unbalance alarms, etc. | ||
Analogous | DC4~20mA,(Load < 500 Ω) (Note: A shielded cable is specially selected for the above signal input and output.) | ||
DI/DO switching | Entrance | 4-channel or 2-channel dry contact input, built-in power supply | |
output | 2-channel switching output, normally open relay contact, power: 3 A/30 VDC, 3 A/250 VAC | ||
Relief supplies | Voltage range | AC/DC 85-265V | |
Power consumption | <5VA | ||
Power frequency withstand voltage | Between power supply terminal set and signal input, output terminal set 2 kV/1 min. (RMS) Between the case and all terminal sets (except the terminal set with a reference voltage of less than 40 V) AC 4 kV | ||
Environment | temperature | Operating: -10℃~+55℃; Storage: -25°C ~+70°C | |
humidity | ≤95 % relative humidity, no condensation, no corrosive gases | ||
Height | ≤ 2500m |