HomeProductsEnergy monitoring and protectionARB arc protection relayARB4 arc protection relay

ARB4 arc protection relay

The ARB4 series arc flash protection device integrates multiple functions such as protection, measurement, monitoring, control, communication, fault recording, and event recording. It can monitor arc flash signals and provide real-time protection for current or voltage signals, and achieve arc flash protection for medium and low voltage distribution systems from 0.4 kV to 35 kV. The ARB4 series arc flash protection device is easy to operate, resource-saving, stable, reliable, and easy to maintain. It is widely used in industries such as power and water, transportation, industry, mineral extraction, renewable energy, shipping, and construction.

  • High-performance hardware platform
  • Mature and perfect protective function
  • Rich interface resources: 4 AC current channels and 3 AC voltage channels; 8 active switching input channels; 5 independent passive switching output channels; 1 RS485 serial communication interface supporting IEC60870-5-103 and Modbus protocols;
  • LCD display, human-machine interface
  • Real-time current and voltage values, arc, input and output
  • Record action behavior and error waveform information
  • Self-test functions, good interference suppression performance
  • Application: Electricity, water conservation, transportation, industry, minerals, new energy, ships and construction buildings

Product info

Selection table for arc protection devices

Selection table for arc sensors

Technical data

Model/Function

ARB4-A1

ARB4-A2

ARB4-A3

Hardware

Signal detection of the arc sensor

1

2

3

Current collection

4 power channels

Voltage detection

3 zero voltages, a total of 3 voltage channels

Digital Input

8

Digital output

5 normally open exits

1 RS485 interface / IRIG-B

function

Arc protection

Arc criterion

Arc and current criterion

 √

Arc and voltage criterion

Arc monitoring and fault location

Real-time self-inspection of arc sensors and fiber optic connections

Device self-test and abnormal alarm

CT interruption monitoring

Non-electrical protection

Device alarm

Maintenance status lock

Fault recording

protocol

Modbus

IEC101

IEC103

IRIG-B

LoopBack

Note: √ indicates that this function is available.

 

Power supply AC/DC 220V, AC/DC 110V, DC 48V, DC 24V
Area Power supply × (1 ± 20 %)
Maximum power consumption ≤ 15 VA
nominal voltage AC 100V or 100/√3 V
Area 0.1–120 V
accuracy ±1 %
Power consumption ≤ 0.5 VA (single-phase)
overload capacity 1.4 times the rated voltage in continuous operation;
2 times for 10 seconds.
Rated current AC 5 A/1 A
Area 0.04 inches to 20 inches
Power consumption ≤ 0.5 VA (single-phase)
Overload capacity 2 times the rated current in continuous operation;
40 times overload in 1 second.
Nominal frequency 50 Hz or 60 Hz
Area 40–70 Hz
accuracy ±0.1 Hz
Mechanical life ≥10,000
Switching capacity ≥1,000 W (L/R = 40 ms)
Inrush current Continuous current ≥5 A, short-term (200 ms) ≥30 A
Breaking capacity ≥30 W (L/R = 40 ms)
Pulse voltage ±5 kV (1.2/50 μs, 0.5 J)

Technical parameters of the ARB-S arc sensor:

The ARB-S arc sensor has a monitoring angle of over 180° and an operating temperature range of -40°C to 85°C.

ARB-S0 Passive wide-angle ultraviolet arc sensor (no power supply, maintenance-free); fully insulated, metal-free (no electrical safety hazards).
ARB-S1 Passive wide-angle ultraviolet arc sensor (no power supply, maintenance-free); ST standard interface.

Product display