Accuracy: | U, I: Class 1.5 |
Frequency range: | 45–65 Hz |
Auxiliary power supply: | AC85V–265V/DC100V–350V |
SOE Event Recorder: | Recording of eight fault messages |
Dimensions (L x W x H): | 81.5 mm x 86 mm x 90 mm |
Installation: | Main body: DIN 35 mm Display unit: panel mounting |
ARD3 motor protection switch
The Acrel ARD3 intelligent motor protection switches can protect motors from numerous faults during operation and display the operating status clearly and intuitively via the LCD. The protection switch features an RS485 remote communication interface and a DC 4-20mA analog output, making it easy to form a network system with control devices such as PLCs and PCs.
Product info
Technical data
Technical parameters | index | |
Protector auxiliary power supply | AC85-265V/DC100-350V, power consumption 15VA | |
Rated operating voltage of the motor | AC380V / 660V, 50Hz / 60Hz | |
Rated operating current of the motor | 1 (0.1A-5000A) | Small special current transformers |
5 (0.1A-5000A) | ||
25 (6.3A-25A) | ||
100 (25A-100A) | ||
250 (63A-250A) | Special current transformers | |
800 (250A-800A) | ||
Contact capacity of the relay output | Impedance load | AC250V, 10A |
Relay output contactor | 5 channels, AC 250 V 6 A | |
Nominal capacity negative | ||
Switching input | 9 channels, optocoupler isolation | |
communication | RS485 Modbus_RTU, Profibus_DP | |
Environment | working temperature | -10ºC~55ºC |
Storage temperature | -25ºC~70ºC | |
Relative humidity | ≤95﹪No condensation, no corrosive gas | |
Height | ≤2000m | |
degree of contamination | Class 2 | |
Degree of protection | Main body IP20, split display module IP54 (installed on the cabinet panel) | |
Plant category | Stage III |