ADL series multifunctional electric energy meter mounted on DIN rail is an intelligent instrument mainly designed for new power generation systems such as grid-connected photovoltaic systems, micro inverter systems, energy storage systems, AC coupling systems, etc. The product has the advantages of high precision, small volume, high response speed and convenient installation. The product has the features of sampling, measuring and monitoring power parameters, communicating with inverter or energy management system (EMS), realizing the functions of preventing backflow, regulating power generation, charging and discharging batteries according to real-time power and accumulated electric energy, and realizing bidirectional measurement and distributed household photovoltaic energy management.

  • Rated voltage: AC 3*230/400V(±20%)
  • Rated current: 80A, 120A, 200A, 300A, 3*80A, 3*120A, 3*200A, 3*300A
  • RS485(MODBUS-RTU:1~247) communication
  • LCD display; 35mm DIN rail mounting
  • Measurement of electrical energy: Active energy measurement (forward and reverse measurement); Reactive energy measurement (forward and reverse measurement)
  • Electrical quantity measurement: U, I, P, Q, S, PF, F
  • Pulse output: Active pulse output
  • Key programming: Optimization, transformation ratio and other parameters can be programmed via the key
  • LED Alarm: User Manual
  • MID certified

Product info

MID Certification Three-Phase DIN-Rail Energy Meter
Measurement accuracy:kWh: Class 0.5
Frequency:45~65Hz
Nominal voltage:AC 3*230/400V(±20%)
input current:80A, 120A, 200A, 300A, 3*80A, 3*120A, 3*200A, 3*300A
Diameter of the transformer perforation: 10mm, 16mm, 24mm, 36mm
Active energy:Class B (split current transformer) 
Reactive energy:(Class 2 accuracy)
Power consumption: ≤2W
Baud rate: Supports 1200 bps-38400 bps
Dimensions:90*45*65mm
Operating temperatur: -40℃~+70℃
Installation:35mm

Technical data

Tension

nominal voltage AC 3*230/400V(±20%)
consumption <2W, <10VA
Accuracy class Error ±0.5 %
Electricity Input current

AC 80A, 120A, 200A, 300A, 3*80A, 3*120A, 3*200A, 3*300A

Accuracy class Error ±0.5 %
consumption <1W, <1VA
Performance Active, reactive, apparent power, error ±0.5 %
frequency of the grid 50/60 Hz, error ±0.5 %
response rate
≤100ms (voltage, current, power)
≤1s (electrical energy)
measurement category CAT III
overvoltage level O OVC III
Energy measurement
Active energy: Class B
reactive energy (accuracy class 2)
Measurement performance accuracy kWh Class 0.5
Area 0~9999999999.99kWh
Beat accuracy Error ≤0.5s/d
Active impulse Width 80±20ms
communication
interface RS485
protocol MODBUS-RTU:1~247
baud rate
1200bps-38400bps
Temperature range Work -40℃~+70℃
storage -40℃~+70℃
humidity ≤95%(No condensation)
Altitude <2000m
reference standard

EN IEC 61010-1:2010 Safety requirements for electrical equipment for measurement, control, and laboratory use - Part 1: General requirements

EN IEC 61010-2-030:2010 Safety requirements for electrical equipment for measurement, control, and laboratory use - Part 2-030: Particular requirements for equipment with test or measuring circuits

EN IEC 61326-1:2021 Electrical equipment for measurement, control and laboratory use - EMC requirements - Part 1: General requirements

EN IEC 61326-2-1:2021 Electrical equipment for measurement, control, and laboratory use - EMC requirements - Part 2-1: Particular requirements for electromagnetic compatibility testing for electrical equipment for measurement, control, and laboratory use

EN 50470-3 Electricity measuring instruments (alternating current) - Part 3: Particular requirements - Static meters for active energy (class indices A, B and C)

IP

IP 51 (Must be installed in a suitable IP housing)
degree of pollution II
UC degree III
installation environment indoor use
degree protect Class II (double insulation)
operating environment Cabinet mounting (the outer shell cannot be touched)
Mechanical quality M1
Safety features of transformers

Insulation resistance: more than 1000 MΩ under normal conditions;

Electrical strength resistance: It can withstand a power frequency of 4000V and 50Hz for 1 minute;