HomeProductsEnergy monitoring and protectionAM Series Medium Voltage Protection RelaysAM4 series medium voltage protection relays

AM4 series medium voltage protection relays

The AM series protection relays are suitable for user substations with an input voltage of 35 kV and below. We use mature technology solutions to ensure the quality of the AM relay. The AM relay is widely used in substations, subsection posts, and ring main units for office buildings, commercial buildings, communication buildings, and mine buildings, etc.

  • A comprehensive set of protection, depending on the application;
  • 4 current inputs, 4 voltage inputs, 12DI, 5DO;
  • Auxiliary power supply adaptable with AC220V, DC220V, DC110V, AC110V;
  • 1 RS485 interface, IEC60870-5-103 and Modbus RTU;
  • 1 RS232 for user updates;
  • 1 GPS for GPS timing;
  • More than 200 event sequence records, more than 400 system logs and more than 10 seconds long trigger context records;
  • Powerful graphically programmable logic.

Product info

Power supply:AC/DC220V or AC/DC110V or DC48V (see circuit diagram)
Nominal voltage: AC100V
Accuracy: ±0.5 %
Rated current: AC 5 A/1 A (see device circuit diagram)
Nominal frequency: 50 Hz or 60 Hz
Mechanical life: ≥10000 times
Switching capacity: ≥1000 W, L/R = 40 ms
Inrush current:continuous ≥ 5 A, short-term (200 ms) ≥ 30 A
Widely used in substations

Technical data

Nominal parameters Power supply AC/DC220V or AC/DC110V or DC48V (see circuit diagram)
Range: Power supply * (1±20%)
Maximum power consumption: ≤10 W (DC)
nominal voltage AC100V
Range: 1-120V
Accuracy: ±0.5%
Power consumption: ≤0.5 VA (single-phase)
Overload capacity: 1.2 times rated voltage for continuous operation; 2 times for 10 seconds
Rated current AC 5A/1A (See device wiring diagram)
Range: 0.04in~15in
Power consumption: ≤0.5 VA (single-phase)
Overcapacity: 2 times rated current for continuous operation; 40 times for 1 second
frequency 50 Hz or 60 Hz
45~55Hz
Accuracy: ±0.1Hz
Digital input AC/DC220V, AC/DC110V, DC48V (Similar to power supply)
Voltage range: Nominal voltage * (1±20%)
Power consumption: ≤1 W (DC 220 V) (single channel)
Digital output Mechanical life: ≥10000 times
Switching power: ≥1000W, L/R=40ms
Inrush current: continuous ≥ 5 A, short-term (200 ms) ≥ 30 A.
Interrupting power: ≥30W,L/R=40ms
Normal working conditions Ambient temperature: -10℃~+55℃
The device can be stored and transported at an ambient temperature of -25 °C to +70 °C.
Relative Humidity: 5 % ~ 95 % (The product does it)
Altitude: ≤4000m

Product display