HomeProductsPower sensorBM Series Analog Signal IsolatorsBM100-DI signal isolator

BM100-DI signal isolator

The BM100 series signal isolators quickly and accurately measure electrical parameters such as current and voltage, as well as non-electrical parameters such as temperature and resistance, and convert them into a standard analog signal after isolation. They can be directly connected to pointer instruments and digital indicators and are also compatible with automatic control devices (e.g., PLCs), various A/D converters, and computer systems. They are widely used in the energy, railway, petrochemical, metallurgical, chemical, food, and warehousing industries, among others.

  • Channel Type: Single Input, Single Output, Single Input, Bidirectional Output, Bidirectional Input and Output
  • Input type: Current/Voltage/Thermal resistance Pt100/Resistance
  • Input signal: DC 0–20 mA / 4–20 mA; DC 0–5 V / 1–5 V / 0–10 V; Pt100 (minimum range: 50 °C); 0–10 kΩ (minimum range: 1 kΩ)
  • Output signal: DC 0~20 mA / 4~20 mA; DC 0~5 V / 1~5 V; DC 0~10 V / 2~10 V
  • Transmission accuracy: 0.2 %
  • 35 mm DIN rail mounting

Product info

Input type;Current/Voltage/Thermal resistance Pt100/Resistance
Input signal:DC 0–20 mA / 4–20 mA
DC 0-5V / 1-5V / 0-10V
Pt100
0–10 kΩ
Output signal:DC 0~20 mA / 4~20 mA
DC 0~5V / 1~5V
DC 0~10 V / 2~10 V
Transmission accuracy:0,2 %
Response time:5 ms to reach 90 % of the final value
Power supply:20-35V DC or 85-265V AC/DC

Technical data

Channel type

Single input, single output,

Single input, bidirectional output,

Bidirectional input and output

Input type Current/Voltage/Thermal resistance Pt100/Resistance
input signal
DC 0~20mA / 4~20mA
DC 0~5V / 1~5V / 0~10V
Pt100 (minimum range: 50 °C)
0–10 kΩ (minimum range: 1 kΩ)
Output signal DC 0-20mA/4-20mA; Load resistance: ≤550Ω
DC 0-5V/1-5V; Load resistance: ≥ 330 kΩ
Load resistance: ≥ 30 kΩ (Pt100/resistance input)
DC 0-10V/2-10V; Load resistance: ≥ 500 kΩ
Load resistance: ≥ 30 kΩ (Pt100/resistance input)
Transmission accuracy
0.2%
Temperature module 50 ppm/℃ (voltage output: 100 ppm/℃)
response time 5 ms to reach 90 % of the final value
(RTD Pt100/resistance input: 1 s to reach 90 % of the final value)
Power supply
20~35V DC or 85~265V AC/DC
working temperature
-20℃~+60℃
Fixed mode DIN rail mounting
Dielectric strength ≥1500 V AC/1 min. (between input/output/power supply)

Product display