| Input type; | Current/Voltage/Thermal resistance Pt100/Resistance |
| Input signal: | DC 0–20 mA / 4–20 mA DC 0-5V / 1-5V / 0-10V Pt100 0–10 kΩ |
| Output signal: | DC 0~20 mA / 4~20 mA DC 0~5V / 1~5V DC 0~10 V / 2~10 V |
| Transmission accuracy: | 0,2 % |
| Response time: | 5 ms to reach 90 % of the final value |
| Power supply: | 20-35V DC or 85-265V AC/DC |
BM200-DI Insulated Safety Barrier
The BM100 series signal isolators quickly and accurately measure electrical parameters such as current and voltage, as well as non-electrical parameters such as temperature and resistance, and convert them into a standard analog signal after isolation. They can be directly connected to pointer instruments and digital indicators and are also compatible with automatic control devices (e.g., PLCs), various A/D converters, and computer systems. They are widely used in the energy, railway, petrochemical, metallurgical, chemical, food, and warehousing industries, among others.
Product info
Technical data
| Channel type |
Single input, single output, Single input, bidirectional output, Bidirectional input and output |
| Input type | Current/Voltage/Thermal resistance Pt100/Resistance/Thermocouple |
| input signal | 0~20 mA / 4~20 mA 0~5V /0~10V /1~5V (Supply voltage: 12V/20mA) PT100 /0~10 K/K, E, T, J, N, R, S, B |
| Output signal | 0–20 mA/4–20 mA (safe side input); load resistance: ≤ 550 Ω 0–5 V/1–5 V (safe side input); load resistance: ≥ 330 K 0–10 V (input on the safe side); load resistance: ≥ 500 K |
| Transmission accuracy |
0.2%
|
| Temperature module | 50 ppm/℃ (voltage output: 100 ppm/℃) |
| response time | 5 ms to reach 90 % of the final value (RTD Pt100/resistance input: 1 s to reach 90 % of the final value) |
| Power supply |
20~35V DC or 85~265V AC/DC
|
| working temperature |
-20℃~+60℃
|
| Fixed mode | DIN rail mounting |
| Dielectric strength | ≥1500 V AC/1 min. (between input/output/power supply) |
Product display