Can connect up to 16 intelligent miniature circuit breakers + intelligent molded case circuit breakers |
LCD display, supports event recording |
DC12V output |
Real-time data such as voltage, current, power, energy, temperature and leakage of various intelligent circuit breakers can be displayed |
Display warnings, alarms, protection, faults and other status information of various intelligent circuit breakers |
Allows setting and controlling parameters for various intelligent circuit breakers |
Support uplink RS485 (standard)/Ethernet/4G communication/Wi-Fi communication |
One switching input and one switching output |
Support for MQTT, MODBUS-RTU and MODBUS-TCP protocols |
ASCB1-MS Intelligent Gateway for Smart Circuit Breakers
The ASCB1 series intelligent microcircuit breakers (hereinafter referred to as intelligent microcircuit breakers) are used in low-voltage distribution networks in industrial, commercial, and civil buildings, as well as in residential infrastructure and similar locations. The intelligent microcircuit breaker is used with the intelligent gateway to monitor key electrical parameters of the power line, such as voltage, current, power, temperature, leakage, energy consumption, and more, in real time. It features remote control, abnormality warning, accident alarm, power measurement statistics, fault location, and other functions.
Product info
Technical data
Model | ASCB1-63 | ASCB1LE-63 | ||
Number of poles | 1P/2P/3P/4P | 2P/4P | ||
Shell quality class | 63A | |||
nominal voltage | 230V(1P/2P)、400V(3P/4P) | |||
Rated current | 6A,10A,16A,20A,25A,32A,40A,50A,63A | |||
Instant unlock type | CD | |||
Rated short-circuit breaking capacity | 6000A | |||
Protection | Overcurrent protection | Default 100% rated current alarm, 110% Rated current trip with adjustable threshold |
||
Short circuit protection | 5-10 rated current for 0.04 seconds to protect against circuit interruption | |||
Overload protection | Standard 100% rated power, 110% rated power with adjustable threshold | |||
Overvoltage protection | Standard 110% rated voltage, 120% rated voltage, triggering with adjustable threshold | |||
Undervoltage protection | Standard 90% rated voltage, 80% rated voltage, triggering with adjustable threshold | |||
Overtemperature protection | Default 80℃ alarm, 100℃ trigger, threshold adjustable | |||
Leakage protection | No | Default 20mA alarm, 30mA trigger, the threshold is adjustable | ||
Leakage self-inspection | No | Manual key self-test | ||
Mechanical life | 20000 times | |||
Electrical life | 6000 times | |||
Protection types | IP20 | |||
Connection capacity | 1-35mm² | |||
Increase requirements | 2000m | |||
Ambient temperature | -10℃~55℃, the average temperature in 24h was not higher than 40℃ | |||
Environmental requirements | No risk of explosion, no conductive dust, no sufficient corrosion of metal and damaged insulation, no significant vibrations | |||
Relative humidity | At + 40℃, the relative humidity is 50% and can have high relative humidity at lower temperatures | |||
Storage temperature | -20℃-70℃ | |||
Class of pollution | 2 | |||
Type of installation | Ⅲ | |||
installation | Standard 35mm rail guide |
ASCB1 Intelligent Gateway
Product model |
ASCB1-M-4G
|
ASCB1-M-CE
|
Power supply |
AC220V
|
|
consumption |
≤30W
|
|
communication
|
4G
|
Ethernet
|
Advertisement | LCD dot matrix | |
Incident recording | Up to 20 alarm, error and action records each | |
Protocol
|
Modbus, MQTT and so on | |
Altitude requirements |
2000m
|
|
Ambient temperature |
-10℃-55℃, the average temperature does not exceed 40 °C over 24 hours
|
|
Environmental requirements | No risk of explosion, no conductive dust, no sufficient corrosion of metal and damaged insulation, no significant vibrations | |
Relative humidity | At +40 °C the relative humidity is 50 % and can have high relative humidity at lower temperatures | |
Storage temperature |
-20℃-70℃
|
|
Protection levels |
IP20
|
|
Assembly instructions | Standard 35 mm guide rail mounting |
Product display
Downloads
Video

similar products