Selection table for arc protection devices

Selection table for arc sensors



| Model/Function |
ARB4-A1 |
ARB4-A2 |
ARB4-A3 |
||
|
Hardware |
Signal detection of the arc sensor |
1 |
2 |
3 |
|
|
Current collection |
4 power channels |
||||
|
Voltage detection |
3 zero voltages, a total of 3 voltage channels |
||||
|
Digital Input |
8 | ||||
|
Digital output |
5 normally open exits |
||||
|
1 RS485 interface / IRIG-B |
√ |
||||
|
function |
Arc protection |
Arc criterion |
√ |
||
|
Arc and current criterion |
√ | ||||
|
Arc and voltage criterion |
√ |
||||
|
Arc monitoring and fault location |
√ |
||||
|
Real-time self-inspection of arc sensors and fiber optic connections |
√ |
||||
|
Device self-test and abnormal alarm |
√ |
||||
|
CT interruption monitoring |
√ |
||||
|
Non-electrical protection |
√ |
||||
|
Device alarm |
√ |
||||
|
Maintenance status lock |
√ |
||||
|
Fault recording |
√ |
||||
|
protocol |
Modbus |
√ |
|||
|
IEC101 |
√ |
||||
|
IEC103 |
√ |
||||
|
IRIG-B |
√ |
||||
|
LoopBack |
√ |
||||
Note: √ indicates that this function is available.
| Power supply | AC/DC 220V, AC/DC 110V, DC 48V, DC 24V |
| Area | Power supply × (1 ± 20 %) |
| Maximum power consumption | ≤ 15 VA |
| nominal voltage | AC 100V or 100/√3 V |
| Area | 0.1–120 V |
| accuracy | ±1 % |
| Power consumption | ≤ 0.5 VA (single-phase) |
| overload capacity | 1.4 times the rated voltage in continuous operation; 2 times for 10 seconds. |
| Rated current | AC 5 A/1 A |
| Area | 0.04 inches to 20 inches |
| Power consumption | ≤ 0.5 VA (single-phase) |
| Overload capacity | 2 times the rated current in continuous operation; 40 times overload in 1 second. |
| Nominal frequency | 50 Hz or 60 Hz |
| Area | 40–70 Hz |
| accuracy | ±0.1 Hz |
| Mechanical life | ≥10,000 |
| Switching capacity | ≥1,000 W (L/R = 40 ms) |
| Inrush current | Continuous current ≥5 A, short-term (200 ms) ≥30 A |
| Breaking capacity | ≥30 W (L/R = 40 ms) |
| Pulse voltage | ±5 kV (1.2/50 μs, 0.5 J) |
Technical parameters of the ARB-S arc sensor:
The ARB-S arc sensor has a monitoring angle of over 180° and an operating temperature range of -40°C to 85°C.
|
|
ARB-S0 | Passive wide-angle ultraviolet arc sensor (no power supply, maintenance-free); fully insulated, metal-free (no electrical safety hazards). |
![]() |
ARB-S1 | Passive wide-angle ultraviolet arc sensor (no power supply, maintenance-free); ST standard interface. |