The ADL200W-ADL400W series DIN-rail-mounted, multifunctional dual-circuit electricity meter with external current transformer is a smart instrument primarily designed for new energy generation systems such as grid-connected photovoltaic systems, microinverter systems, energy storage systems, and AC coupling systems. The product offers the advantages of high precision, small size, high response speed, and easy installation. It can monitor and measure power and other performance parameters in real time, supports protocols such as Modbus-TCP and HTTP, and communicates with inverters or energy management systems (EMS) via Wi-Fi or Lora to achieve functions such as backflow prevention, power generation regulation, and battery charging and discharging. It enables bidirectional measurements to enable energy management for distributed photovoltaic systems in homes.

  • Single-phase: 230 V
  • Accuracy: 0.5
  • DIN 35 mm

Product info

Technical data

function Descriptions
Measurement of electrical energy Active energy measurement (forward and backward)
Reactive energy measurement (forward and reverse)
Split-phase energy
Electrical quantity measurement U, I
P, Q, S, PF, F
communication RS485, Wi-Fi, Lora
 
Item Performance parameters
Model series ADL200W ADL400W
 

 

 

 

 

 

 

measurement

Grid Single-phase Three-phase, four-wire
 

 

 

 

voltage

(Unom) Nominal voltage 230V 3×230/400V
input area 0.8Unom ~ 1.2Unom
Overload 1.2-fold rating (continuous) 2

 

2x rating for 1 second

Power consumption <2W, <10VA
Accuracy class Error ±0.5%
 

 

 

Electricity

Minimum current (Imin) 0.3A
Transient current (Itr) 1.5A
Base current (Ib) 30A
Maximum current (Imax) D16:Imax = 120A
Short-term overcurrent 30 times the maximum current for 20 ms
Power consumption <1W, <1VA
Accuracy class Error ±0.5 %
power Active, reactive, apparent power, error ±1.0℅
   
  Mains frequency 50Hz, error ±0.5 %
Response rate 50ms (voltage, current, power)
Installation category CAT III
Overvoltage level OVC III
measurement Active electrical energy Class 1 or B
Electromagnetic compatibility E2
 

Security

Power frequency withstand voltage Between communication and signal input, AC3kV 1min
Insulation resistance Input and output connections to the housing > 100 MΩ

 

communication

RS485 interface Modbus RTU protocol; Address: 1~247; Baud rate: 1200 bps - 38400 bps
Wi-Fi Protocols: Modbus-TCP, HTTP, etc. Operating frequency band: 2.4 GHz
 

 

 

Environment

Operating temperature range -25℃~+55℃
Operating temperature range -40℃~+70℃
Storage temperature -40℃~+85℃

 

Relative humidity

≤95% (without condensation)

 

“Not suitable for humid environments”

Height

≤2000m

 

IP protection class

IP20

on terminal block without protective housing and IP51 in protective housing according to IEC 60529

Pollution Degree II
UC Degree III
installation environment Interior
Degree of protection Class II (double insulation)
Usage environment Mounted in the cabinet (the outer shell must not be touched)
Usage environment M1
Safety features of the transformer Insulation resistance: greater than 1000 MΩ under normal conditions