ANSVG Static Var Generator

Acrel power quality devices are primarily used in power supply and distribution on the consumer side, providing power quality improvement devices (e.g., active filters, power factor correction systems, etc.) to improve power quality and increase consumer efficiency, safety, and reliability. The Acrel ANSVG series power factor and harmonic compensation devices are connected in parallel throughout the power system, detect signals via transformers, and control the internal power factor compensation module and active filter module according to changes in the load power factor and harmonic content in the power grid. Power compensation and active filtering are also available.

  • 380V ± 15 %, 50Hz ± 2 %
  • Full response time ≤ 5 ms
  • 30kVAR, 50kVAR, 75kVAR or 100kVAR
  • RS485 (Modbus RTU) or Ethernet (Modbus TCP)
  • Frozen data

Product info

Switching frequency:20 kHz
Response time:Full response time ≤ 5 ms, instantaneous response time ≤ 100 μs
Total harmonic compensation rate:≥ 97 % , 3rd/5th/7th/9th independent compensation rate ≥ 98 %
Dimensions (L x W x H):450 x 622 x 201 mm
Loss of self:≤2%

1) Flexible compensation method: compensation of the reactive power of the load, filtering out harmonics of the 5th, 7th, 9th, 11th and 13th harmonics;

2) Compensation of three-phase asymmetries;

3) Linear compensation, response time ≤ 5 ms;

4) User-friendly human-computer interface for displaying real-time information on the system's power quality and ontology. This interface enables remote control of the device and is easy to use;

5) Use of imported IGBTs with high power density and high reliability;

6) Using a digital DSP control system for fast detection and calculation;

7) With remote communication interface and real-time monitoring via PC;

8) Standard modular design for shorter delivery times and greater reliability and ease of maintenance.

Technical data

wiring
3P3W or 3P4W
Voltage input
380V
frequency 50Hz
Reactive power compensation The target power factor can be set as desired
Number of harmonic compensation 2nd–31st harmonics
communication RS485 Modbus RTU
Protection class IP30, customizable
Color RAL7035, customizable
installation Internal mounting, fixed mounting and cable entry optional
operating temperatur -10℃-+45℃
Operating humidity 40℃:≤50%RH,20℃:≤90%RH
Height <2000m

Product display