ASJ10-LD1A leakage relay

Acrel ASJ series post-current action relays, low-voltage circuit breakers, or low-voltage contactors can be combined into post-current generation devices, primarily used for TT and TN system distribution circuits with 50 Hz AC and a rated voltage of 400 V or less. ASJ series post-current action relays are used for ground fault protection of electrical circuits to prevent equipment damage and fires caused by ground fault currents. They also provide indirect contact protection against the risk of electric shock.

  • Measurement of type A residual current
  • Streamer display of current in percent
  • Setting the rated residual current
  • Setting the limit of the non-operation time
  • Two-pair relay output
  • On-site and long-distance testing and reset function

Product info

Frequency:50 Hz ± 5 Hz
Auxiliary power supply:AC 110 V, AC 220 V, DC 85–270 V (permissible error ± 10 μs)
Consumption:≤ 5 W
Assembly:DIN rail 35 mm
Dimensions (L x W x H):85 × 54 × 64 mm

Technical data

type function installation Look
ASJ10-LD1C AC fault current measurement;
Alarm message in case of current overshoot;
Measurement of the nominal fault current;
Adjustable downtime limitation;
Two relay outputs;
With local and remote test and reset function.
(DIN rail 35 mm)
ASJ10-LD1A Residual current measurement type A;
Light column display in percent;
Measurement of the nominal fault current;
Adjustable downtime limitation;
Two adjustable relay outputs (Note 1);
With local and remote test and reset functions.
ASJ10L-LD1A Note 2 Residual current measurement type A;
Nominal fault current measurable;
Limit for downtime adjustable;
Two relay outputs adjustable;
Transformer break alarm adjustable;
Pre-alarm value adjustable;
Return value adjustable.
With on-site display, remote test and reset.
LCD display, 25 event recordings.
ASJ20-LD1C AC fault current measurement;
Alarm message in case of current overshoot;
Measurement of the nominal fault current;
Adjustable downtime limitation;
Two relay outputs;
With local and remote test and reset function.
Panel (48 x 48)
ASJ20-LD1A Residual current measurement type A;
Light column display in percent;
Measurement of the nominal fault current;
Adjustable downtime limitation;
Two adjustable relay outputs (Note 1);
With local and remote test and reset functions.

Note 1: Relay settings allow you to configure the initialization and output state of the relay yourself via code selection on the control panel. Detailed setting instructions can be found in Chapter 5.2.
Note 2: Optional function: RS485 interface, Modbus RTU communication, type ASJ10L-LD1A/C

 

Technical parameters indicator
AC type
A type
Power supply Voltage range
AC110V、AC220V(±10%)
AC/DC85~265V
Power consumption
≤5W
Entrance
Rated residual current I△n
0.03, 0.1, 0.3, 0.5(A)
0.03、0.05、0.1、0.3、0.5、1、3、5、10、30(A)Note 3
Limitation of non-driving time △t
0.1, 0.5(s)
0、0.06、0.1、0.2、0.3、0.5、0.8、1、4、10(s)Note 4
Rated residual current in quiescent state I△no
50%I△n
50%I△n
Features Sinusoidal AC Sinusoidal AC and pulsating DC
frequency
50Hz±5Hz
50Hz±5Hz
Area of application
-20% ~ -10%I△n
-20% ~ -10%I△n
output Output mode One is normally open, the other is used for transformation One is normally closed or open, the other is used to transform
Contact capacity
5A 250VAC
5A 30VDC
AL1: 8A 250VAC; 5A 30VDC
AL2: 6A 250VAC; 5A 30VDC
Reset mode Local reset or remote reset Local reset, remote reset or automatic reset
Installation and usage environment
temperature
Operating temperature: -20 °C to +55 °C, storage temperature: -30 °C to +70 °C
humidity
≤95%RH, no condensation and no corrosive gases
elevation
≤2000m
degree of contamination Grade three
Installation category
Type II

Note 3: The rated residual current IΔn of the ASJ10L-LD1A is continuously adjustable from 10 mA to 30 A.
Note 4: The maximum rest time Δt of the ASJ10L-LD1A is continuously adjustable from 0 to 10 s.

Product display