APM801 AC Multifunctional Energy Meter

APM series grid electricity meters are designed according to IEC standards and have functions such as complete power measurement, power statistics, power quality analysis and grid communication. They are mainly used for comprehensive monitoring and diagnosis of power supply quality and power management. The meters in this series have a modular design.

  • Rated current: -/5A AC; -/1A AC (via current transformer)
  • Rated voltage: 100V, 110V, 400V, 690V AC
  • Frequency: 45~65Hz
  • Measurement accuracy: 0.2S
  • Dimension: 96*96*90mm (L*W*H)
  • Power supply: 85~265V AC/DC; 115~415V AC/DC
  • Protection class: Display IP52
  • Certificates: CE

Product info

AC Multifunctional Energy Meter
Measurement:3-phase kWh, kVarh, kW, I, U, Hz, Cosφ, current and voltage asymmetry, 2~63rd harmonics, real-time and maximum demand, zero sequence current, 4-quadrant energy, etc.
Rated current:-/5A AC; -/1A AC (via current transformer)
Nominal voltage:100V, 110V, 400V, 690V AC
Frequency:45~65Hz
Measurement accuracy:0.2S
Communication (main part):RS485 (MODBUS RTU)
Communication (Advanced):PROFIBUS-DP; Ethernet; Secondary RS485
Extra function:8DI/2DO; 8AI/4AO; SOE (with standard 4GB SD card); Multirate
Advertisement:LCD display
Dimension:96*96*90mm(L*W*H)
Installation:Built-in panel (cutout - 92*92mm)
Power supply:85~265V AC/DC; 115~415V AC/DC

Technical data

Model APM801
signal power grid Three-phase three-wire, three-phase four-wire
frequency 45~65Hz
Tension Rated value: AC 100V、110V、400V、690V
Overload: 1.2 times rated value (continuous); 2 times rated value /1 second
Power consumption: < 0.5VA (per channel)
Electricity Rated value: AC 1A, 5A, supports 4 mm2 line access
Overload: 1.2 times rated value (continuous); 10 times rated value/1 second
Power consumption: < 0.5VA (per channel)
Measurement accuracy Voltage, current and power Class 0.2S
Active power Class 0.2S
Reactive power Class 2.0
Switching inputs Dry contact inputs, integrated power supply
Relay outputs Contact type open contact in the main part, changeover contact in the module
Capacity of the contact AC 250V/3A DC 30V/3A
Impulse delivery of energy Output mode Optocoupler pulse with open collector
Pulse constant 4000(5A), 8000(1A) imp/kWh
Analog outputs  DC 0mA~20mA, 4mA~20mA, 0V~5V, 1V~5V output, accuracy class 0.5%, load resistance ≤ 500Ω
Analog inputs DC 0mA~20mA, 4mA~20mA, 0V~5V, 1V~5V input, accuracy class 0.5%
Memory card Standard Capacity 4G
maximum capacity TF card up to 32G capacity
communication RS485 interface/Modbus-RTU protocol and DLT645 protocol
Profibus-DP interface/Profibus-DP protocol
RJ45 interface (Ethernet) / Modbus-TCP, http, DHCP and other protocols
Power supply Workspace AC/DC 85V~265V or AC/DC 115~415V(P2)
Power consumption Power consumption of main body ≤ 15VA
Security Mains frequency withstand voltage The mains frequency withstand voltage between the housing and the auxiliary power supply and each input and output terminal group is AC 4kV/1min
The mains frequency withstand voltage between the auxiliary power supply and each input and output terminal group is AC 2kV/1min
The power frequency withstand voltage between the voltage input and other input/output terminal groups is AC 2kV/1min
The mains frequency withstand voltage between the power input and the other input/output terminal groups is AC 2kV/1min
The power frequency withstand voltage between the relay output and other input/output terminal groups is AC 2kV/1min
The power frequency withstand voltage between each terminal group of the switching input, communication, analog output and pulse output is AC 1kV/1min
Insulation resistance Inputs, outputs to the housing>100MΩ
Electromagnetic compatibility Complies with IEC 61000 (Level 4)
Protection level Display field IP52
Environment operating temperatur -20°C~ +65°C
Storage temperature -20°C~ +70°C
Relative humidity ≤95% without condensation
Altitude ≤2500m
Standards IEC60068-2-1 Environmental testing-Part 2-1:Tests Test A:Cold IDA
IEC60068-2-2 Part 2-1:Tests Test B:Dry heat
IEC60068-2-30 Part 2-30:Tests Test Db:Damp heat, cyclic (12+12h)
IEC61000-4 Electromagnetic compatibility testing and measurement methods
IEC61557-12 Electrical safety in low-voltage distribution systems up to 1000 V a.c. and 1500 V d.c. - Equipment for testing, measuring or monitoring of protective measures - Part 12: Power measuring and monitoring devices (PMD)
IEC62053-22 Electricity metering devices operating under alternating current - Particular requirements - Part 22: Static meters for active energy of classes 0.2s and 0.5s.
IEC62053-24 Electricity meters operating under alternating current - Particular requirements - Part 24: Fundamental frequency static reactive energy meters (classes 0.5S, 1S and 1)