HomeProductsEnergy managementAPM Series Panel Multifunction Energy MeterAPM510 Multifunctional Energy Meter

APM510 Multifunctional Energy Meter

The APM5 series network power meter (hereinafter referred to as the meter) is designed according to international IEC standards and features full power measurement, power statistics, power quality analysis (including harmonics, interharmonics, and flicker), fault recording (including temporary voltage spikes and dips, inrush current, and other recordings), event recording, network communication, and other functions. It is primarily used for comprehensive power quality monitoring in electrical networks. This series of meters is equipped with feature-rich DI/DO modules, AO modules, wireless communication modules, and leakage temperature measurement modules, enabling flexible implementation of full electrical circuit power measurement and switching state monitoring.

  • Full power measurement
  • Network quality analysis
  • Leakage current measurement (optional)
  • Supports Modbus RTU/TCP protocol
  • Accuracy: 0.5 s
  • Standards and certifications: CE

Product info

APM510 (72*72)Measurement of all electrical parameters (class 0.5s), neutral current, imbalance, mean value, extreme value, 2DI+2DO, RS485 communication (Modbus RTU protocol), 1Ep pulse output, 2-63 harmonics
APM520 (96*96)Measurement of all electrical parameters (class 0.5s), neutral current, imbalance, mean value, extreme value, 4DI+2DO, RS485 communication (Modbus RTU protocol), 2Ep pulse output, 2-63 harmonics

Technical data

Basic model

basic function

Optional function

Option group

APM510

2DI2DO1EP1C

1. CE (Ethernet Communication/MODBUS-TCP).

1+5+6+7+8

2+3+4+7+8

5+6+7+8+9

5+6+7+8+10

5+6+7+8+11

5+6+7+8+12

2.2C (Extended Second Communication).

3.K (2 switch inputs + 2 switch outputs).

4.2M (2ch analog).

5.T (4-channel NTC temperature measurement).

6.L (1 channel leakage current).

7.F (Multirates).

8.S (0.2S class + error recording).

9.WF (WiFi Communication)

10.LR (Lora Communication)

11.4G (4G communication)

12.NB (NB Communication)

Basic model

basic function

Optional function

Option group

APM520

4DI2DO2EP1C

1. CE (Ethernet Communication/MODBUS-TCP).

1+5+6+7+8

2+3+4+7+8

1+5+6+7+8

2+3+4+7+8

5+6+7+8+9

5+6+7+8+10

5+6+7+8+11

5+6+7+8+12

2.2C (Extended Second Communication).

3.K (4 switch inputs + 2 switch outputs).

4.2M (2ch analog).

5.T (4-channel NTC temperature measurement).

6.L (1 channel leakage current).

7.F (Multirates).

8.S (0.2S class + error recording).

9.WF (WiFi Communication)

10.LR (Lora Communication)

11.4G (4G communication)

12.NB (NB Communication)

Note: 1. Optional K-function, defined as an extension of the DID based on the basic function

Advertisement Display method Dot matrix liquid crystal; Switch between Chinese and English
resolution 128*128;
Backlight white LED
Visible area 72 Shape: 38mm*46mm (1.78"/2.3");
96 Shape: 56mm*60mm (2.46"/3.2");
signal Electrical network Three-phase three-wire, three-phase four-wire, see the wiring diagram;
frequency 45~65Hz;
Tension Rating: AC 3*57.7/100V, AC 3*63.5/110V, AC 3*230/400V, AC 3*400/690V (96 shape only);
Overload: 1.2 times the mention (continuous); 2x rating/1 second;
Power consumption: < 0.5VA (in any mode);
Storm Ratings: AC 3x 1 (1,2) A, AC 3 × 5 (6) A;
Overload: 1.2 times the mention (continuous); 10x rating/1 second;
Power consumption: < 0.5VA (in any mode);
Measurement accuracy Voltage, current IEC 61557-12 0.2%
Voltage harmonics, current harmonics IEC 61557-12 1%
frequency IEC 61557-12 ±0.02Hz
Active performance IEC 61557-12 0.5%
Reactive power IEC 61557-12 1%
Active electrical energy 0.5S class GB/T 17215.321-2008C class GB/T 17215.321-2021 (accuracy of 0.2S when S is selected)

Product display